Within a major leading edge manufacturing company, a test bed put extreme demands on the power supply network. In this case study, an ADF installation compensates harmonics up to the 100th order resulting in significant reduction of notching.
BackgroundThe development department within a major european plant owns several test benches to test certain components in their products during the development phase. Different test conditions can be programmed, giving the test bench extremely dynamic properties. ChallengeTwo parts of the test bench are connected to the same transformer. The load is very dynamic and the amplitude of the load current can change from zero to its maximum in approximately 100 ms. Both parts of the test bench could not be run at the same time, because of the high harmonic disturbances and voltage notches up to 25 %. Apart from exceeding the limits in EN61000-2-4, this also caused serious delay in the testing facility. Solution –
|
Before:
|
After:
|
Tel: +46 46 286 35 00 • Fax: +46 46 286 35 05
E-mail:info@comsys.se