IEEE 1547a aims at maintaining sustainable power delivery during the faulty conditions and the generation units ride through the low voltage conditions and
Source: Low voltage ride through in grid connected hybrid renewable energy systems | EEP
IEEE 1547a aims at maintaining sustainable power delivery during the faulty conditions and the generation units ride through the low voltage conditions and
Source: Low voltage ride through in grid connected hybrid renewable energy systems | EEP
On which Power Quality subjet would you like more information ?
Total Voters: 28
Variable-frequency-drive- (VFD-) generated harmonics largely is a perceived, rather than real, issue. In 27 years of applying VFDs in HVAC and other applications, this author has experienced only a handful of actual harmonics problems, with all but one stemming from high levels of voltage distortion, not the current distortion that has been getting so much attention lately.
Most of the VFD-interference problems this author has encountered have been the result of poor installation — particularly, poor wiring and grounding. In the majority of cases, radio-frequency interference (RFI) or electromagnetic interference (EMI), not harmonics, was the culprit. RFI/EMI issues stem from noise in the 50-Khz-to-low-megahertz range, not the 300-Hz fifth or 420-Hz seventh harmonic range.
In 1981, ANSI/IEEE Standard 519, IEEE Guide for Harmonic Control and Reactive Compensation of Static Power Converters, was published. It included maximum total-harmonic-voltage-distortion (THDV) recommendations.
In the extreme, voltage distortion can cause flat-topping of power-system voltage waveforms (Figure 1), which can cause sensitive electronic processors to become confused and malfunction.
In 1992, ANSI/IEEE Standard 519 was revised. Renamed IEEE Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems, it now concentrates more on total harmonic current distortion (THD1) than voltage distortion.
THD1 can propagate through utility step-down/step-up transformers and make its way from one facility to another. For example, several years ago, a VFD manufacturer was creating high amounts of current distortion during its burn-in testing operation. The current distortion traveled through the utility transformers at the VFD manufacturer’s plant to the utility feed at a neighboring printing plant, corrupting the logic circuits in the controls and direct-current (DC) drives running the printing plant’s printing press and causing the printing-press registration to malfunction.
THD1 results in additional heat in the distribution transformers typically provided by utilities, as well as the power-feeder cables of the equipment from which it originates. Basically, THD1 is current that a utility has to generate and source to a facility, but that brings no revenue to the utility. While it is a real issue for utilities, THDI largely is a perceived problem from a facility manager’s point of view.
ANSI/IEEE Standard 519-1992 addresses the system-issue nature of THD1 by introducing total demand distortion (TDD), which can be calculated as follows:
where:
Ihe = total harmonic current as measured by system
Ihc = total harmonic current contributed by VFDs
IL = maximum demand-load current (fundamental frequency component) (15- or 30-min demand) at utility point of common coupling (PCC) as measured in system
IC = fundamental frequency component contributed by vfds (included only if vfds are an addition to existing loads)
(All quantities are in amperes root mean square.)
ANSI/IEEE Standard 519-1992 states, “Within an industrial plant, the PCC is the point between the nonlinear load and other loads.” Many consulting engineers have interpreted this to mean that THD1 is to be measured at VFD input-power connections (PCC2, instead of PCC1, in Figure 2). This misapplication of ANSI/IEEE Standard 519-1992 has contributed to the overuse of multipulse drives in the HVAC industry. Many millions of facility-equipment dollars have been squandered through the specification and installation of 12- and 18-pulse drives in commercial office buildings and other environments in which a standard six-pulse drive would have done the same job for substantially less upfront cost.
Also unfortunate is the fact ANSI/IEEE Standard 519-1992 has five different levels of acceptable maximum TDD, which depend on the ratio of maximum short-circuit current (ISC) to maximum IL at a PCC. The ISC-to-IL ratios in Table 1 are functions of the strength of a utility’s feed to a facility and the size of the substation transformer.
Many specifications simply state, “VFDs shall meet ANSI/IEEE Standard 519.” Such a statement is meaningless without the information needed to perform harmonic calculations:
Calculations are even more accurate when manufacturers have additional information, such as facility total current, existing harmonic content, and wire sizes and lengths.
Some engineers have taken to writing hardware specifications based on horsepower size requirements. For example: “All VFDs 100 hp and up shall be 18-pulse designs.” At 100 hp, an 18-pulse drive easily can cost four times as much as a six-pulse drive with no improvement in energy savings.
That is not to say there are no applications for which a 12- or 18-pulse drive is appropriate. Take, for instance, a cinderblock pump station in a residential neighborhood. This author observed one in which there were three 300-hp VFDs, overhead fluorescent lighting, and a wall-mounted programmable logic controller (PLC). The pump station was fed by a dedicated 480-v transformer. Virtually the entire load on the transformer was non-linear. The VFD non-linear load represented approximately 1,100 amps. The PLC and fluorescent-light loads totaled a couple of amps. That was an ideal application for 18-pulse or other ultralow-harmonic VFD technology.
In a commercial office building, if VFDs are installed on every fan and pump, they typically will use less than 20 percent of the electrical demand load. In almost all such cases, standard six-pulse drives are a good choice.
Contrary to popular belief, ANSI/IEEE Standard 519 is not a law or government/utility regulation; it is a “recommended practice.” It states that strict adherence to its recommended harmonic limits “will not always prevent problems from arising.” The contrary also is true: A facility may have harmonics in excess of the standard’s maximum recommended limits and not experience difficulties.
The simplest and least-expensive method of mitigating VFD-generated harmonics is adding impedance at a VFD. This can be accomplished with an input line reactor (Figure 3) or a DC link reactor (bus choke) (Figure 4). In a 1-percent-source-impedance system, a 3-percent line reactor can reduce harmonic-current content at the input to a VFD to about 40 percent at full-load output.
The next-most-common type of harmonic-mitigation technology is the 12-pulse VFD (Figure 5). A 12-pulse VFD reduces harmonic-current content to about 10 percent.
Also common are broad-band and passive filters (Figure 6). These hybrid filters reduce harmonic-current content to approximately 7 percent.
The next-most-effective technology is the 18-pulse drive (Figure 7), which typically presents approximately 5-percent current distortion at VFD inputs. Compared with a VFD with no impedance, total harmonic reduction is in the range of 93 percent.
Relatively new technologies are the active harmonic filter (Figure 8) and the active-front-end VFD (Figure 9). A single active filter can filter the harmonics of several VFDs or an entire facility. Meanwhile, the THDI content of a VFD with an active front end — measured at the VFD input — typically is less than 4 percent, while the total-harmonic-current-content reduction is 95 percent.
Table 2 lists the expected current distortion, percent current-distortion reduction, and relative cost of the various harmonic-reduction technologies. The estimates are based on a 1-percent-source-impedance system and a perfectly balanced voltage supply.
All hardware-based, “brute-force” methods of harmonic reduction are affected negatively by input-power-system voltage imbalances. Most VFD manufacturers have computer programs that can be used to estimate harmonic distortion from VFDs.
The greater the base load on a substation transformer, the lesser the current distortion at a PCC. Because harmonic-current distortion causes additional transformer heating, utilities often oversize substation transformers relative to the loading expected from a facility. As a result, having the correct maximum transformer load (estimated or measured) is vital. Otherwise, maximum transformer IL must be assumed.
Most harmonic-analysis programs assume available power is a balanced voltage — for example, 480 v each on Phase A, Phase B, and Phase C. In the real world, however, no matter how well-designed a building distribution system is, perfect balance is unobtainable. The best one can hope for is a slight imbalance, such as 478:480:482 v. Most utilities allow power-voltage imbalances of up to 3 percent.
Many years ago, at a large university in the Midwest, the VFDs provided in an energy-saving retrofit project were being blamed for buildings exceeding the distortion levels recommended in ANSI/IEEE Standard 519. Harmonic analysis showed substantial third-harmonic content. In a perfect world, VFDs do not create third harmonics, as third and other triplen harmonics cancel because of the three-phase nature of VFDs. If, however, the voltage relationship between phases A, B, and C is unbalanced, cancelation cannot occur completely, and VFDs can create triplen harmonics. In this case, Phase A was approximately 450 v, while phases B and C were close to 480 v. The university was asked to move loads to get the input voltage to a more balanced condition. Once that was done, the VFDs stopped causing elevated levels of harmonic distortion.
During the mid-1990s, the Power Electronics Applications Center, a subsidiary of the Electric Power Research Institute, tested the drives of 17 manufacturers.1 A 0.2-percent voltage imbalance at the input lugs of a VFD with no input line reactor or DC-bus choke was found to cause up to a 17-percent current imbalance.
With an unbalanced input-power system, all hardware-based harmonic-mitigation technologies are subject to detrimental harmonic-cancelation effects. For example, a 12-pulse phase-shifting transformer has three input leads and six output leads and two components: a delta/delta winding set and a delta-wye winding set (Figure 10). This configuration causes a 30-degree electrical-phase shift in the power being fed into one of the drive’s two diode bridges, causing, in a perfect world, fifth and seventh harmonics to be canceled. If input power is unbalanced, however, cancelation will not occur completely.
Some VFD manufacturers supply 18-pulse drives with an additional 5-percent impedance reactor in front of the auto transformer. This helps balance the current draw into the auto transformer’s three sets of windings and helps to minimize the effects of unbalanced voltage and source feeds.
The most effective means of obtaining ultralow harmonics at VFD inputs is an active filter or an active front end. An active filter works like an active noise-reduction headset. If, for example, it detects a 30-amp fifth harmonic in Phase A of a power supply, it injects 30-amp fifth harmonic 180 degrees out of phase with the VFD-created harmonic, creating a cancelation effect. This technology is less susceptible to incoming-voltage imbalances because it measures and injects corrective harmonic content automatically.
A few manufacturers make ultralow-harmonic VFD technologies. An ultralow-harmonic VFD has six insulated-gate bipolar transistors (IGBTs), rather than passive diode-bridge components, in its convertor section (Figure 11). These IGBTs control the harmonic current drawn by a VFD. With no harmonic current drawn, no cancelation is required. Ultralow-harmonic technology typically reduces input harmonic currents to 4 percent or less at a VFD input (Table 2).
In one test, a 3-percent voltage imbalance on the input of an 18-pulse transformer/drive caused a 1.5-percent-per-unit increase in current distortion. Thus, if the computer harmonic-analysis estimate had been 4 percent, actual THDI would have been 5.5 percent.
With an ultralow-harmonic or active-filter system, a 3-percent voltage imbalance increases harmonic-current distortion by less than 0.5 percent per unit.
A harmonic analysis should be performed before a design is finalized. The analysis should be conducted at the PCC to determine current distortion at the main utility service entrance to a building. Hardware-based specifications dictating that any drives over a certain horsepower shall be a certain technology should not be utilized.
1) Mansoor, A., Phipps, K., & Ferro, R. (1996). System compatibility research: Five horsepower pwm adjustable-speed drives. Knoxville, TN: Power Electronics Applications Center.
For past HPAC Engineering feature articles, visit www.hpac.com.
The manager of HVAC applications for ABB Inc. Power & Control Sales, Michael R. Olson has extensive experience in the HVAC, water/wastewater-treatment, and chemical industries. He has written numerous trade-journal articles discussing the application of adjustable-speed drives and been a contributing editor to several books on the subject. He has a bachelor’s degree in electrical engineering from the University of Illinois and a master’s degree in engineering management from the Milwaukee School of Engineering. He is a member of the American Society of Heating, Refrigerating and Air-Conditioning Engineers and BACnet International. He can be contacted at mike.olson@us.abb.com.
Posted May 29 2012 by Sufi Shah Hamid Jalali in Energy Efficiency, Lighting on Electrical Engineering Portal
Original Source: Wolsey, Robert, Power Quality, Volume 2, Number 2, February 1995 (Lighting Research Center (LRC) and Power Quality),
Power factor is a measure of how effectively a device converts input current and voltage into useful electric power. Mathematically it is defined as follows:
Power factor triangle
Where P is active power and S is the apparent power.
It is often confused with: Continue reading
Concerns about the effects of lighting products on power distribution systems have focused attention on power quality. Poor power quality can waste energy and the capacity of an electrical system; it can harm both the electrical distribution system and devices operating on the system.
There are many elements in a power system that affects two major parameters; power factor and harmonics. Electric motors, some lighting fixtures, transformers and other inductive and capacitive appliances introduce reactive power to the system, and thus involved in damaging the power factor. These components need reactive power to work.
Nonlinear loads like UPS, computer systems, fluorescent fixtures, CFLs, digital electronics, etc. are distorting current waveforms and introducing harmonics to the power system.
Source : mepca Engineering
Vacon UK – Using variable speed drives (VSDs) is a great way of saving energy but, if your VSDs are more than five years old, it’s time to take another look at them, says Stephen Takhar, Managing Director of ac variable speed drive expert, Vacon UK.
For the last decade, the technical press has been awash with stories about the energy savings that can be made by fitting VSDs. The stories are true, which is why many companies have already installed VSDs. When engineers in these companies see the VSD energy saving stories, they probably think they’ve been there and done that, but are they justified in sitting back and enjoying the glow of a job well done? That depends on the age of their VSDs. If they’re just a few years old, it’s unlikely that further action is needed. But if the VSDs are over five years old, it’s a different story. Continue reading
Here are some guidelines to produce an informative Power Quality case studies that will help to sell your skills or mitigating solutions. These sections should be covered:
Country | Frequency (Hz) and tolerance (%) | Household voltage (V) | Commercial voltage (V) | Industrialv oltage(V) | Voltage tolerance(%) |
Albania | 50 + 0.5 | 220/380 | 220/380 | 220/380 • 6 kV – 10 kV | +5 |
Algeria | 50 ±1 | 220 | 380/220 | 380/220 • 30 kV (rural)10 kV (urban) | ±10 |
Andorra | 50 +1 | 230400 | 230400 | 230 • 400 | +6/-10 |
Angola | 50 ±5 | 380/220 • 220 | 380/220 | 400/231 | ±10 |
Antigua and Barbuda | 60 | 400/230 • 120/208 | 400/230 • 120/208 | ||
Argentina | 50 ±2 | 220 | 380/220220 | 380/220 | ±8 |
Armenia | 50 ±0.4 | 380/220 • 220 | 380/220 • 220 • 110 kV35 kV/6 kV •10 kV | 380/220 • 220 • 110 kV35 kV/6 kV • 10000 kV | ±5 |
Australia | 50 ±0.1 | 400/230 | 400/230 | 400/230 | +10/-6 |
Austria | 50 ±1 | 230 | 400/230 | 400/230 | ±10(400/230) |
Azerbaijan | 50 ±0.4 | 380/220 • 220 | 380/220220 | 380/220 | ±5 |
Barhain | 50 ±2 | 415/240 • 240400/230 | 415/240 • 240400/230 | 11 kV • 415/240240 • 400/230 | ±6 |
Bangladesh | 50 ±2 | 400/230 | 400/230 | 11 kV • 400/230 | ±10 |
Belarus | 50 ±0.8 | 380/220 • 220220/127 • 127 | 380/220 • 220 | 380/220 | Normally ±5Maxi 10 |
Belgium | 50 ±3 | 230 • 400/230 | 230 • 400/230 | From 3 to 15.5 kV | +6/-10 |
Benin | 50 ±5 | 220 | 220 to 380 | 15 kV/380V | ±10 |
Bolivia | 50 ±5 | 230 | 400/230 • 230 | 400/230 | +5/-10 |
Bosnia Herzergovina | 50±0.2 | 380/220 • 220 | 380/220 • 220 | 10 kV • 6.6 kV380/220 | ±8±5 |
Brazil | 60 | 220/127 | 380/220 • 220-127 | 380/220 • 440/254 | +5/-7.5 |
Bulgaria | 50 ±0.1 | 220/230 | 220/230 | 380 | ±10 |
Burkina faso | 50 ±10 | 230 | 400 | 400 | ±10 |
Burundi | 50 ±1 | 380/220 | 400/230 | 400/230 • 66 kV/400-23010 kV/400-23030 kV/400-230 | ±10 |
Cambodia | 50 ±0.5 | 220 | 380/220 | 380/220 | ±5 |
Cameroun | 50 ±1 | 220-260 | 260-220 | 380/220 | +5/-10 |
Canada | 60 ±2 | 240/120240 | 347/600 • 416/240208/120 • 600 | 46 kV • 34.5 kV/20 kV24.94 kV/14.4 kV 13.8 kV/8 kV12.47 kV/7.2 kV
4.16 kV/2.4 kV • 600/347 |
+4/-8.3 |
Canary island | 50 ±5 | 220 | 220/380 | 380/220 | ±5 |
Cape Verde | 50 | 220 | 220/380 | 380/400 • 20 kV • 6 kV15 kV • 13 kV • 10 kV | ±5 |
Central African Republic | 50 ±4 | 220/380 | 15 kV • 220/380 | 15 kV • 220/380 | ±10 |
Chad | 50 ±1 | 220 | 220 | 380/220 | Not available |
Chile | 50 ±0.2 | 220 | 380 | 13.8 kV • 13.2 kV12 kV • 440 • 380 | ±3.5 |
China | 50 ±0.2 | 220 | 380220 | 380220 | ±7+7/-10 |
Colombia | 60 ±0.2 | 240/120 • 208/120 | 240/120 • 208/120 | 44 kV • 34.5 kV • 13.8 kV(11.4 kV Bogota only) | +5/-10 |
Congo (Democratic Republic) | 50 | 220/240 | 380/220 | 380/220 • 6.6 kV20 kV • 30 kV | ±10 |
Costa Rica | 60 | 240/120 | 240/120 • 208/120 | 240/120 • 208/120400/277 | ±5 |
Cote d’Ivorie | 50 ±2 | 230/400 | 15 kV • 19 kV • 43 kV | 15 kV • 19 kV • 43 kV | +6/-10 |
Crotia | 50 | 400/230 • 230 | 400/230 • 230 | 400/230 | ±10 |
Cuba | 60 ±1 | 115/230 | 230/400 | 230/400 | ±10 |
Cyprus | 50 ±2.5 | 230/400 | 230/400 | 22/11 kV • 230/440 | ±10 |
Czech republic | 50 ±1 | 230/400 | 230/400 • 500690 | 400 kV • 220 kV • 110 kV35 kV • 22 kV • 10 kV6 kV • 3 kV | +6/-10 |
Denmark | 50 ±1 | 400/230 | 400/230 | 400/230 | +6/-10 |
Djibouti | 50 | 220 | 400/230 | 400/230 • 20 kV | ±10 |
Dominican republic | 60 | 240 | 240/120 | 7.2 kV • 480 • 220/110208 • 115 | ±3 |
Ecuador | 60 ±1 | 110 | 110 | 440/220 | ±5 |
Egypt | 50 ±0.5 | 380/220 • 220 | 380/220 • 220 | 132 kV • 66 kV • 33 kV20 kV • 22 kV • 11 kV6.6 kV • 380/220 | ±10 |
Estonia | 50 ±1 | 380/220 • 220 | 380/220 • 220 | 380/220 | ±10 |
Ethiopia | 50 ±2.5 | 220 | 380/230 | 15 kV • 45 kV • 132 kV230 kV • 380/230 | ±10 |
Fiji | 50 ±2 | 415/240 • 240 | 415/240 • 240 | 11 kV • 415/240 | ±6 |
Finland | 50 +/0.1 | 230 • 400 | 400/230 | 400/230 • 690/400 • 690/40010 kV • 20 kV • 110 kV | +6/-10 |
France | 50 ±1 | 400/230 • 230 | 400/230 • 690/400 | 20 kV • 10 kV • 400/230 | +6/-10 |
French Guiana | 50 | 220 | 230/ 400 | 15 kV • 20 kV • 30 kV • 400 | Not available |
Georgia | 50 ±0.5 | 380/220 | 380/220 | 380 • 6 kV • 10 kV | ±10 |
Germany | 50 ±0.5 | 400/230 • 230 | 400/230 • 230 | 20 kV • 10 kV • 6 kV690/400 • 400/230 | +6/-10 |
Ghana | 50 ±5 | 240-220 | 240-220 | 415-240 | ±10 |
Greece | 50 | 230 | 230/400 | 400 | +6/-10 |
Grenada | 50 | 230 | 400/230 | 400/230 | +4/-8 |
Guadeloupe | 50 and 60 | 220 | 380/220 | 20 kV • 380/220 | Not available |
Honduras | 60 ±3 | 220/110 | 480/277 • 240/120 | 69 kV • 34.5 kV • 13.8 kV480/277 • 240/120 | + ou-5 |
Hong Kong | 50 ±2 | 380/220 | 380/220 | 11 kV • 380/220 | ±6 |
Hungary | 50 ±1 | 230/400 | 230/440 | 230/400 | ±10 |
Iceland | 50 ±0.1 | 230 | 400/230 | 400/230 | +6/-10 |
India | 50 ±3 | 440 • 230 | 400 • 230 | 11 kV • 440/250 | ±10 |
Indonesia | 50 | 220 • 220/380 | 220/380 | 150 kV • 70 kV • 20 kV | ±5 |
Iran | 50 ±5 | 220 | 380/220 | 20 kV • 400/230 • 380/220 | ±5 |
Iraq | 50 | 220 | 380/220 | 11 kV • 6.6 kV3 kV • 380/220 | ±5 |
Ireland | 50 ±2 | 230 | 400/230 | 10 kV • 20 kV • 38 kV110 kV • 400/230 | +6/-10 |
Israel | 50 +0.5/-0.6 | 400/230 | 400/230 | For above 630 kVA:12.6 kV/22 kV/33 kV/110 kV/161 kV | ±10 |
Italy | 50 ±2 | 400/230 • 230 | 400/230 | 20 kV • 15 kV10 kV • 400/230 | ±10 |
Japan | 50 (east) / 60 (west) | 200/100 | 200/100(up to 50 kW) | 140 kV • 60 kV • 20 kV6 kV • 200/100 | ±6V(101V)±20V(202V)6-140 kV |
Jordan | 50 | 230 | 400/230 | 415/240 • 3.3 • 6.6 • 11 kV | ±7 |
Kenya | 50 ±2.5 | 240 | 415/240 | 415/240 | ±6 |
Korea republic of south | 60 ±0.2 | 220 ±13 • 110 ±10 | 380 ±38V • 220 ±13 | 20.8 kV • 23.8 kV380 ±38V • 380/220 | Not available |
Kuwait | 50 ±4 | 230 | 400/230 | 400/230 | +10/-10 |
Latvia | 50 ±0.4 | 380/220 • 220 | 380/220 • 220 | 380/220 | +10/-15 |
Lebanon | 50 | 220 | 380/220 | 380/220 | ±10 |
Lybian | 50 ±1 | 220 | 220/380 | 38011 kV | ±10 |
Lithuania | 50 ±1 | 400/230 | 400/230 | 400/230 | ±10 |
Luxembourg | 50 ±0.0 | 400/230 | 400/230 | 65 kV • 20 kV | +6/-10 |
Macedonia | 50 | 380/220 • 220 | 380/220 • 220 | 10 kV • 6.6 kV • 380/220 | Not available |
Madagascar | 50 ±2 | 220/110 • 380/220 | 220/110 • 380/220 | 63 kV • 35 kV • 30 kV20 kV • 15 kV5.5 kV • 380/220 | Low voltage: ±7Hight voltage: ±5 |
Malaysia | 50 ±1 | 240415/240 | 415/240 | 415/240 | +5/-10 |
Mali | 50 | 220380/220 | 220 • 380/220 | Not available | Not available |
Malta | 50 ±2 | 230 | 400/230 | 11 kV • 400/230 | +10/-6 |
Martinique | 50 | 230 | 230/400V • 230 | 230/400 • 20 kV | -10/+6 |
Mauritania | 50 | 380/220 | 380/220 | 15 kV • 380/220 | ±10 |
Mauritius | 50 ±1 | 230 | 400/230 | 400/230 | ±6 |
Mexico | 60 ±0.2 | 220/127 • 220 • 120 | 220/127 • 220 • 120 | 13.8 kV • 13.2 kV480/277 • 220/127 | ±10 |
Morocco | 50 ±5 | 380/220 | 380/220 | 225 kV • 150 kV60 kV • 22 kV | ±10 |
Netherlands | 50 ±10 | 400/230 • 230 | 400/230 | 25 kV • 20 kV • 12 kV10 kV • 230/400 | ±10 |
New Zealand | 50 ±1.5 | 400/230 • 230 | 400/230 • 230 | 11 kV • 400/230 | ±6 |
Nigeria | 50 ±1 | 230 • 220 | 400/230 • 380/220 | 15 kV • 11 kV400/230 • 380/220 | ±5 |
Norway | 50 ±1 | 400/230 | 400/230 | 400/230 • 690 | ±10 |
Pakistan | 50 | 230 | 400/230 • 230 | 400/230 | ±5 |
Paraguay | 50 ±5 | 220 | 380/220 • 220 | 22 kV • 380/220 | ±5 |
Peru | 60 ±6 | 220 | 220 | 20 kV • 10 kV • 220 | ±5 |
Poland | 50 +0.2/-0.550 +0.4/-1 | 230 | 400/230 | 1 kV • 690/400400/230 • 6.3 kV | +6/-10 |
Portugal | 50 ±1 | 400/230 • 230 | 60 kV • 30 kV • 15 kV10 kV • 400/230 • 230 | 60 kV • 30 kV • 15 kV10 kV • 400/230 • 230 | 60 ±10 |
Qatar | 50 ±1 | 240 | 415/240 | 33 kV • 66 kV • 132 kV | ±5 |
Romania | 50 ±0.5 | 230 | 440/230 | 660/380400/230 | ±10 |
Russia | 50 ±0.2 | 380/220 • 220 | 660/380/220380/220/127 | 660/380/220380/220/127 | +10/-20 |
Rwanda | 50 ±1 | 220 | 380/220 | 15 kV • 6.6 kV • 380/220 | ±5 |
Saudi Arabia | 60 ±0.3 | 220/127 | 220/127 | 13.8 kV • 380/220 | ±5 |
Senegal | 50 ±5 | 220 | 380/220 • 220/127 | 90 kV • 30 kV • 6.6 kV | ±10 |
Serbia | 50 | 230/400230 | 230/440230 | 10 kV • 6.6 kV • 230/400 | ±10 |
Singapore | 50 ±1 | 400/230 • 230 | 400/230 | 22 kV • 6.6 kV • 400/230 | ±6 |
Slovakia | 50 ±0.5 | 230/030 | 230/400 | 230/400 | ±10 |
Slovenia | 50 ±0.1 | 230/400 | 230/400 | 35 kV • 20 kV • 10 kV • 6 kV3.3 kV • 1000V • 660V500V • 400/230 | +6/-10 for 400/230 |
Somalia | 50 | 230 • 220 • 110 | 440/220 • 220/110230 | 440/220 • 220/110 | ±10 |
South Africa | 50 ±2.5 | 433/250 • 400/230380/220 • 220 | 11 kV • 6.6 kV • 3.3 kV433/250 • 400/230380/220 | 11 kV • 6.6 kV • 3.3 kV500 • 380/220 | ±10 |
Spain | 50 ±0.5 | 380/220 • 220220/127 • 127 | 380/220 • 220/127 | 25 kV • 20 kV • 15 kV11 kV • 10 kV • 6 kV3 kV • 380/220 | ±7 |
Sudan | 50 | 240 | 415/240 • 240 | 415/240 | Not available |
Sweden | 50 ±0.5 | 400/230 • 230 | 400/230 • 230 | 6 kV • 10 kV • 20 kV400/230 | +6/-10 |
Switzerland | 50 ±2 | 400/230 | 400/230 | 20 kV • 16 kV • 10 kV • 3 kV1 kV • 690/400 • 950/400 | ±10 |
Syrian Arab Republic | 50 | 380/220 • 220 | 380/220 • 220220/115 | 380/220 | ±5 |
Thailand | 50 ±5 | 220 | 380/220220 | 380/220 | Not available |
Tunisia | 50 ±2 | 380/220 • 231/400242/420 | 380/220 • 231/400242/420 | 30 kV • 15 kV • 10 kV | ±10 |
Turkey | 50 ±1 | 380/220 | 380/220 | 36 kV • 15 kV6.3 kV • 380/220 | ±10 |
Ukraine | 50 +0.2/-0.4 | 380/220 • 220 | 380/220 • 220 | 380/220220 | +5/-10 |
United Arab Emirates(ADWEA) | 50 ±0.5 | 415/240 | 415/240 | 11 kV • 415/240 | ±5 |
United Arab Emirates(DEWA) | 50 ±1 | 380/220 | 380/220 | 11 kV • 6.6 kV • 380/220 | ±3 |
United Arab Emirates(SEWA) | 50 ±1 | 415/240 | 415/240 | 11 kV • 6.6 kV • 415/240 | ±5 |
United Arab Emirates(FEWA) | 50±1 | 415/240 | 415/240 | 11 kV • 415/240 | ±5 |
United KingdomExcluding Northern Ireland | 50±1 | 230 | 400/230 | 22 kV • 11 kV • 6.6 kV3.3 kV • 400/230 | +10/-6 |
UK Northern Ireland | 50±0.4 | 230 • 220 | 400/230 • 380/220 | 400/230 • 380/220 | ±6 |
(USA) North Carolina | 60 ±0.06 | 240/120 • 208/120 | ±10%240 • 480/277460/265 • 240/120
208/120 |
±10%24 kV • 14.4 kV • 7.2 kV2.4 kV • 575 • 460 • 240
460/265 • 240/120 • 208/120 |
+5/-2.5 |
(USA) Michigan | 60 ±0.2 | 240/120 • 208/120 | 480 • 240/120208/120 | 13.2 kV • 4.8 kV • 4.16 kV480 • 240/120 • 208/120 | +4/-6.6 |
(USA) California | 60 ±0.2 | 240/120 | 4.8 kV • 240/120 | 4.8 kV • 240/120 | ±5 |
(USA) Miami | 60 ±0.3 | 240/120 • 208/120 | 240/120 • 208/120 | 13.2 kV • 2.4 kV480/277 • 240/120 | ±5 |
(USA) New York | 60 | 240/120 • 208/120 | 240/120 • 208/120240 | 27.6 kV • 13.8 kV • 12.47 kV4.16 kV • 480/277 • 480 | Not available |
(USA) Pittsburgh | 60 ±0.3 | 240/120 | 460/265 • 240/120208/120 • 460 • 230 | 13.2 kV • 11.5 kV • 2.4 kV460/265 • 208/120460 • 230 | ±5 (ligthning)±10 (power) |
(USA) Portland | 60 | 240/120 | 480/277 • 240/120208/120 • 480 • 240 | 19.9 kV • 12 kV • 7.2 kV2.4 kV • 480/277208/120 • 480 • 240 | Not available |
(USA) San Francisco | 60 ±0.08 | 240/120 • 208/120 | 480/277 • 240/120 | 20.8 kV • 12 kV • 4.16 kV480 • 480/277 • 240/120 | ±5 |
(USA) Ohio | 60 ±0.08 | 240/120 • 208/120 | 480/277 • 240/120208/120 | 12.47 kV • 7.2 kV • 4.8 kV4.16 kV • 480480/277 • 208/120 | ±5 |
Uruguay | 50 ±1 | 220 | 220 • 3×220/380 | 15 kV • 6 kV • 2203×220/380 | ±6 |
Venezuela | 60 | 120 | 480/277 • 208/120 | 13.8 kV • 12.47 kV4.8 kV • 2.4 kV | Not available |
Vietnam | 50 ±0.1 | 220 | 380/220 | 500 kV • 220 kV • 110 kV35 kV • 22 kV • 15 kV10 kV • 6 kV • 3 kV |
As a Power Quality Expert, it is important to have the right contacts in order to get the right information to specify an effective solution. Here are a few of you important contacts and a list of questions that you may want to ask. Continue reading
Source: Advances in Power Electronics Volume 2013 (2013), Article ID 591680, 10 pages http://dx.doi.org/10.1155/2013/591680
Faculty of Engineering, Sohar University, P.O. Box 44, 311 Sohar, Oman
Academic Editor: Hadi Y. Kanaan
A growing number of harmonic mitigation techniques are now available including active and passive methods, and the selection of the best-suited technique for a particular case can be a complicated decision-making process. The performance of some of these techniques is largely dependent on system conditions, while others require extensive system analysis to prevent resonance problems and capacitor failure. A classification of the various available harmonic mitigation techniques is presented in this paper aimed at presenting a review of harmonic mitigation methods to researchers, designers, and engineers dealing with power distribution systems. Continue reading